S12-1.0/115AC Ibex Battery Systems
Maximum Operating Ratings
Line Voltage (Note 1)
Ambient Temperature (Note 2)
Output Short Circuit Duration
Reverse Battery Connection Duration
Hi-Pot Rating (Note 3)
Voltage Isolation (Note 4)
Line Frequency
Storage Temperature
110/220 to 126/252VRMS
-40C to +85C
Continuous
Continuous
1500VRMS
150V
50/60Hz
-55C to +105C
Block Diagram

Operation Manual

General Description

Mechanical Info.

Electrical characteristics Unless stated otherwise, these specifications are valid over the operating temperature range.
Parameter Conditions Minimum Maximum Units
Max. Output Current (Note 5) Ambient = below +65C
Ambient = above +65C
1.0
0.5
2.0
1.0
A
Short Circuit Current - 0 3.0 A
Absorption Mode Voltage Ambient = +85C
+65C
20C
0C
-40C
13.2
13.7
14.6
15.0
15.9
13.7
14.5
15.0
15.7
16.0
V
Float Mode Voltage Ambient = +85C
+65C
20C
0C
-40C
12.3
12.7
13.6
14.0
14.9
12.8
13.3
13.8
14.5
15.4
V
Output Ripple Voltage (Note 6) - - 50 mV pk-pk
Output Leakage (Note 7) - - -0.5 mA
LED Terminal Output Current - 10 20 mA

Note 1: For full output current. The unit remains in regulation at considerably lower line voltages although at a lower maximum output current.
Note 2: Above +65C, the output current is reduced. Attempting to operate the unit above +85C causes the unit to shut down. The unit automatically restarts when the board ambient temperature falls below +85C.
Note 3: 1 minute rating between the line-input terminals and the output terminals or ground.
Note 4: Continuous rating between the output terminals and ground. Mounting the PCB with nylon standoffs and nylon screws increases the output isolation to 1500V.
Note 5: Output voltage = Float Voltage. At lower voltages, the maximum output current ramps up to the maximum short-circuit value
Note 6: Assumes the output is connected to a minimum recommended size battery
Note 7: This is the reverse current that the battery supplies to the charger when the line voltage is removed.

sealed lead acid battery charger chargers sla battery charger chargers vrla battery charger chargers sealed lead acid battery chargers sla gel gell gelcell gellcell gellcel gelcel 12v 12 24v 24 volt volts charger recharger rechargers power supply supplies ups trickle trickel openframe low temperature low temp low cost scada power source scada power backup scada battery backup scada battery source scada ups scada low voltage ups scada lv ups low voltage ups lv ups 12v ups 24v ups 6v ups 6v battery backup 12v battery backup 24v battery backup extreme environment charger -40c +85c battery charger high temp temperature battery charger