L24-0.3/115AC Ibex Battery Systems
Maximum Operating Ratings
Line Voltage
Output Short Circuit Duration
Reverse Battery Connection Duration
Hi-Pot Rating (Note 1)
Output Voltage Isolation (Note 2)
Line Frequency (Min. & Max.)
Operating Temperature
Storage Temperature
103/206 to 126/252VRMS
Continuous
Continuous
2500VRMS
150V Peak
50/60Hz
0C to +40C
-25C to +85C
Block Diagram

Operation Manual

General Description

Mechanical Info.

Electrical characteristics Unless stated otherwise, these specifications are valid over the operating temperature range.
Parameter Conditions Minimum Maximum Units
Max. Output Current (Note 3) Vfoldback < Vout 0.3 0.35 A
Foldback Current (Note 3) Short Circuit 0.05 0.15 A
Absorption Mode Voltage Ambient = +40C
23C
0C
28.4
29.0
29.8
29.6
30.0
31.6
V
Float Mode Voltage Ambient = +40C
23C
0C
26.6
27.2
28.0
27.0
27.6
29.0
V
Output Ripple Voltage (Note 4) - - 100 mV pk-pk
Output Leakage (Note 5) - - -100 uA
LED Connector Output Current - 10 20 mA

Note 1: 1 minute rating between the line-input terminals and the battery output, LED terminals, or ground.
Note 2: Continuous rating between the output terminals and ground when mounted on metal standoffs. Mounting on 3/8" nylon spacers with #6 nylon screws raises the isolation rating to that of the power transformer (2500V RMS).
Note 3: Battery voltage = 12V or higher during charging. Below 12V (Vfoldback), the current folds back linearly to the minimum value (at 0V).
Note 4: Assumes the output is connected to a minimum recommended size battery.
Note 5: This is the reverse current that the battery supplies to the charger when the line voltage is removed.
sealed lead acid battery charger chargers sla battery charger chargers vrla battery charger chargers sealed lead acid battery chargers sla gel gell gelcell gellcell gellcel gelcel 12v 12 24v 24 277 277vac volt volts charger recharger rechargers power supply supplies ups trickle trickel openframe low temperature low temp low cost scada power source scada power backup scada battery backup scada battery source scada ups scada low voltage ups scada lv ups low voltage ups lv ups 12v ups 24v ups 6v ups 6v battery backup 12v battery backup 24v battery backup extreme environment charger -40c battery charger high temp temperature battery charger